Operation instruction
1.Model number and specification
| Product series | W5 | W5 series | ||||||||
| Control | SP | Single-phase angle control | ||||||||
| SZ | Single-phase zero crossing control | |||||||||
| TP | Three-wire three-phase angle control | |||||||||
| TZ | Two-wire three-phase zero crossing control | |||||||||
| ZZ | Three-wire three-phase zero crossing control | |||||||||
| Main power voltage | 1V | 110VAC (Only for single-phase power source) | ||||||||
| 4V | 200~480VAC | |||||||||
| Normal rated current | 030 | 30A | ||||||||
| 045 | 45A | |||||||||
| 060 | 60A | |||||||||
| 080 | 80A | |||||||||
| 100 | 100A | |||||||||
| 125 | 125A | |||||||||
| 150 | 150A | |||||||||
| 180 | 180A | |||||||||
| 230 | 230A | |||||||||
| 300 | 300A | |||||||||
| 380 | 380A | |||||||||
| 450 | 450A | |||||||||
| 580 | 580A | |||||||||
| 720 | 720A | |||||||||
| Dash | - | |||||||||
| Auxiliary power source code | 1 | 1Ø 110VAC | ||||||||
| 2 | 1Ø 220VAC | |||||||||
| Input signal code | 0 | 0~ 5VDC | ||||||||
| 1 | 1~ 5VDC | |||||||||
| 2 | 2~10VDC | |||||||||
| 3 | 0~10VDC | |||||||||
| 4 | 4~20mA | |||||||||
| 5 | 0~20mA | |||||||||
| M | Manual adjustment | |||||||||
| * | Special | |||||||||
| Buffering time code | C | Buffering time 2 seconds (Zero-crossing type product) | ||||||||
| J | Adjustable buffering time, 1~22 seconds (Phase-angle type product) | |||||||||
| Special code | TF | Inductive reactance type loading | ||||||||
| CL | Limited current type | |||||||||
| CV | Fixed voltage type | |||||||||
2.Selection of input signal:
![]() |
![]() |
|||
| P1 |
|
|||
| Selection S1 |
|
Input signals 4~20mA?0~20mA?MANUAL |
||
| Selection S2 |
|
Input signals 1~5VDC?0~5VDC |
||
| Selection S3 |
|
Input signals 2~10VDC?0~10VDC |
||
3.Adjustable Functions:
| VR1 BIAS: | Standard output voltage adjustment. (Counter-clockwise adjust the control signal, lower the input will produce the output.) |
| VR2 SFS : | Buffer rising time adjustment. (Adjusting range 1~22 seconds, clockwise adjustment will increase the time. No applicable for zero crossing type product.) |
| VR3 Max : | Maximum output voltage adjustment. (Adjusting range 0~100%, counter-clockwise adjustment will decrease the output. Set to zero will have no output.) |