Product Features
- Independent adjustment of Max and BIAS.
- Down-opened Panel, easy for fuse replacement.
- VR of Max and SFS are installed in the front panel, easy for adjustment.
- Multi-LED display panel makes the operating condition clear.
- The auxiliary powers (AC1, AC2) are independently controlled for all
models.
- Build-in buffering output adjustment (SFS VR), adjusting range 1~22
seconds. (Only for the phase control product)
- Top & bottom shielding covers are designed for safety and fashion
out looking, also easy for wiring installation.
- In case of 0.5 Hz sudden power losses, system output can be switched
off immediately. Once the power is restored, the system will buffer the
output to prevent the voltage surge for fuse burn-down.
- Main power is one spec. Design for 200~480VAC.
- Automatic power frequency detection for 50~60 Hz. No need for selection
or switch.
- Automatic detection and display for power out-of-phase, SCR overheating,
and fuse burn-down with one set of alarm dry contact output.
- In cases of SCR overheating or fuse burn-down, the system output is
stopped immediately. Once the malfunction is eliminated and power is restored,
the system will buffer the output to prevent the fuse burn-down.
- 4~20mA, 1~5VDC, 2~10VDC, 0~20mA, 0~5 VDC, 0~10VDC, dry contact points,
etc. and all control signals are ready to use.
- Triggering circuit and the main board are designed separately to avoid
the main board damage when main circuit malfunctions.
- Using European detachable control signal connector for easy replacement
without re-wiring installation.
Installation and ambient conditions
- When the power regulator is operating, the heat will be generated
auto- matically. Please install the system vertically and leave
some empty space on two sides to avoid the temperature inside the
regulator rising continuously.
- There must be some ventilation holes on the control box. Please
follow the principle of hard air rising to install the ventilation
holes or extra cooling fans.
- Please avoid installing the regulator in the place with high temperature
or poor ventilation. Otherwise, the maximum operating capacity must
be set lower than 70% of the nominal capacity.
- Avoid installing the regulator in the places with heavy water
evaporation, acid, alkaline, or corrosive air.
- Ambient humidity: below 90%RH (no condensation)
- Ambient temperature: :-10°C~45°C
|
|
Normal
rated capacity %
|
The above numbers are based
on the conditions of no erosion, no greasy dirt, and no cover on
the heat sink and following the re- commended installation guides
based on the principle of heat transfer.
|
|