LED lamp indication and trouble shooting
| Pos. NO. |
Color |
Indicating condition |
Causes of malfunction |
Treatment and trouble shooting |
PL
(L1) |
Green |
No indication of power supply lamp.
Lamp lighting means normal. |
- No power of Aux. source.
- Malfuntion on PCB board.
- Over temperature of SCR.
|
- Check the Aux. power supply.
- Repair or replace the PCB board.
- Check the SCR temperature.
|
IN
(L2) |
Green |
No indication of input lamp.
Lamp lighting means normal. |
- No output signal from TIC.
- Output signal from TIC is reverse.
- Max value of internal output or External VR is zero setted.
|
- Check the output signal of TIC.
- Reverse the connect wiring of TIC.
- Check the setting of internal and external VR output.
|
OUT
(L3) |
Red |
No indication of output lamp.
Phase angle control-lamp lighting means normal.
Zero crossing control-lamp blinks means normal. |
- No output signal from TIC or reverse the connecting of output signal
- Lamp IN lighting and lamp OUT on indication.
- Lamp OUT lighting but no current output.
|
- Check the lamp IN, NO indication means no output signal from TIC or reverse wired.
- Repair or replace the PCB board in case of the malfunction from the board.
- Check main power supply of fuse.
|
ERR
(L4) |
Yellow |
Over-temp of SCR lamp light.
Lamp lighting means SCR over temp. |
- Malfunction or dirt blocking on the ventilation fan.
- High ambient temperature or poor ventilation.
|
- Replace or clean the dirt of the impeller.
- Improve the ventilation condition.
|