LED lamp indication and trouble shooting


Pos. NO. Color Indicating condition Causes of malfunction Treatment and trouble shooting
PL
(L1)
Green No indication of power supply lamp.

Lamp lighting means normal.
  • No power of Aux. source.
  • Malfuntion on PCB board.
  • Over temperature of SCR.
  • Check the Aux. power supply.
  • Repair or replace the PCB board.
  • Check the SCR temperature.
IN
(L2)
Green No indication of input lamp.
Lamp lighting means normal.
  • No output signal from TIC.
  • Output signal from TIC is reverse.
  • Max value of internal output or External VR is zero setted.
  • Check the output signal of TIC.
  • Reverse the connect wiring of TIC.
  • Check the setting of internal and external VR output.
OUT
(L3)

Red
No indication of output lamp.

Phase angle control-lamp lighting means normal.

Zero crossing control-lamp blinks means normal.
  • No output signal from TIC or reverse the connecting of output signal
  • Lamp IN lighting and lamp OUT on indication.
  • Lamp OUT lighting but no current output.
  • Check the lamp IN, NO indication means no output signal from TIC or reverse wired.
  • Repair or replace the PCB board in case of the malfunction from the board.
  • Check main power supply of fuse.
ERR
(L4)
Yellow Over-temp of SCR lamp light.

Lamp lighting means SCR over temp.
  • Malfunction or dirt blocking on the ventilation fan.
  • High ambient temperature or poor ventilation.
  • Replace or clean the dirt of the impeller.
  • Improve the ventilation condition.